| Type Test Reports |
| Equipment Type |
Standard |
Test Carried Out |
Certificate No. |
| 415V, 3200A LV Control Panel |
IS 8623 Part-I-1993
IEC 60493 Part-I-1985 |
Temperature Rise Test at 3200 Amp |
DCCD-11071(A) Dated 01.09.2009 |
| 415V, 3200A LV Bus Duct |
IS 8623 Part-I-1993
IEC 60493 Part-I-1985 |
Temperature Rise Test at 3200 Amp |
DCCD-11071(B) Dated 01.09.2009 |
| Low Voltage Switchgear and Control Assembly- LT Panel (Without Breaker in Circuit) |
Sub Clause 8.2.3 of IS 8623 (Part I): 1993
IEC Pub 439-1 (1985) (Reaffirmed 2004) |
Verification of the short circuit withstand strength i.e. 50kA rms for 1second with 105kA Peak on phase bus bars |
SC09472A
Dated 01.09.2009 |
| Low Voltage Switchgear and Control Assembly-Bus Way |
Sub Clause 8.2.3 of IS 8623 (Part I): 1993
IEC Pub 439-1 (1985) (Reaffirmed 2004) |
Verification of the short circuit withstand strength i.e. 50kA rms for 1second with 105kA Peak on phase bus bars |
SC09472B
Dated 01.09.2009 |
| 415V, LT Panel |
IEC 13947 (Part-I) 1993 |
Degree of Protection IP-55 |
2009/STL/683
Dated 04.09.2009 |
| 12kV, 1250A, Indoor VCB Panel |
IEC:62271-200, 2003 |
Short time and peak withstand tests i.e. 26.3kArms for 1.0 sec. with initial peak of 65.75kA |
S2110127
Dated 11.02.2011 |
| 12kV, 1250A, Indoor VCB Panel |
IEC:62271-200, 2003 |
Degree of Protection IP-4X |
2011/STL/146
Dated 11.05.2011 |
| 12kV, 1250A, Indoor VCB Panel |
IEC:62271-200, 2003 |
Lightning impulse withstand test at 75kVpeak |
2011/STL/263
Dated 05.05.2011 |
| 12kV, 1250A, Indoor VCB Panel |
IEC:62271-200, 2003 |
Dry power frequency voltage withstand test at 28kVrms for 1 minute |
2011/STL/263
Dated 05.05.2011 |
| 12kV, 1250A, Indoor VCB Panel |
IEC:62271-200, 2003 |
Short time and peak withstand tests i.e. 26.3 kArms for 1.0 sec with initial peak of 65.75 kA |
2011/STL/263
Dated 05.05.2011 |