Type Test Reports
Equipment Type Standard Test Carried Out Certificate No.
415V, 3200A LV Control Panel IS 8623 Part-I-1993
IEC 60493 Part-I-1985
Temperature Rise Test at 3200 Amp DCCD-11071(A) Dated 01.09.2009
415V, 3200A LV Bus Duct IS 8623 Part-I-1993
IEC 60493 Part-I-1985
Temperature Rise Test at 3200 Amp DCCD-11071(B) Dated 01.09.2009
Low Voltage Switchgear and Control Assembly- LT Panel (Without Breaker in Circuit) Sub Clause 8.2.3 of IS 8623 (Part I): 1993
IEC Pub 439-1 (1985) (Reaffirmed 2004)
Verification of the short circuit withstand strength i.e. 50kA rms for 1second with 105kA Peak on phase bus bars SC09472A
Dated 01.09.2009
Low Voltage Switchgear and Control Assembly-Bus Way Sub Clause 8.2.3 of IS 8623 (Part I): 1993
IEC Pub 439-1 (1985) (Reaffirmed 2004)
Verification of the short circuit withstand strength i.e. 50kA rms for 1second with 105kA Peak on phase bus bars SC09472B
Dated 01.09.2009
415V, LT Panel IEC 13947 (Part-I) 1993 Degree of Protection IP-55 2009/STL/683
Dated 04.09.2009
12kV, 1250A, Indoor VCB Panel IEC:62271-200, 2003 Short time and peak withstand tests i.e. 26.3kArms for 1.0 sec. with initial peak of 65.75kA S2110127
Dated 11.02.2011
12kV, 1250A, Indoor VCB Panel IEC:62271-200, 2003 Degree of Protection IP-4X 2011/STL/146
Dated 11.05.2011
12kV, 1250A, Indoor VCB Panel IEC:62271-200, 2003 Lightning impulse withstand test at 75kVpeak 2011/STL/263
Dated 05.05.2011
12kV, 1250A, Indoor VCB Panel IEC:62271-200, 2003 Dry power frequency voltage withstand test at 28kVrms for 1 minute 2011/STL/263
Dated 05.05.2011
12kV, 1250A, Indoor VCB Panel IEC:62271-200, 2003 Short time and peak withstand tests i.e. 26.3 kArms for 1.0 sec with initial peak of 65.75 kA 2011/STL/263
Dated 05.05.2011
 